Bared copper conductor is also known as copper stranded conductor. Specially suitable for application in:
● Overhead transmission system
● Overhead traction system
● Transformer earthing(occasionally)
● For grounding electrical systems where high conductivity and flexibility is required.
For any more information or advice please contact the office on 0086-18832134509 (WhatsApp/WeChat)
Details
Conductor Sections
Conductor: Hard-drawn stranded Copper Wire
Standards
Basic design to EN13602/BS 7884/ASTM B8/JIS C 3105:1994/AS1746 standards.
Technical Data
EN 60228(*if other standards are required, please contact with us) | |||||
Nominal Cross Sectional Area | No. of Wires | Diameter of Wires | Diameter of Conductor | Nominal Weight | Maximum DC Resistance at 20℃ |
mm² | mm | mm | kg/km | Ω/km | |
16 | 7 | 1.7 | 5.1 | 137 | 1.15 |
25 | 7 | 2.13 | 6.9 | 215 | 0.727 |
35 | 7 | 2.52 | 7.56 | 300 | 0.524 |
50 | 10 | 2.52 | 8.9 | 410 | 0.387 |
70 | 14 | 2.52 | 10.7 | 595 | 0.268 |
95 | 19 | 2.52 | 12.6 | 820 | 0.193 |
120 | 24 | 2.52 | 14.25 | 1040 | 0.153 |
150 | 30 | 2.52 | 15.75 | 1280 | 0.124 |
185 | 37 | 2.52 | 17.64 | 1600 | 0.0991 |
240 | 48 | 2.52 | 20.3 | 2100 | 0.0754 |
300 | 61 | 2.52 | 22.68 | 2700 | 0.0601 |